Definition of Operating Conditions
This category applies to centralized heating systems for urban residential areas, residential complexes, and commercial buildings. Key parameters include: a heating medium of low-temperature hot water, a design temperature ≤75°C, a design pressure ≤1.0 MPa, and pipe diameters ranging from DN50 to DN355. This scenario-free from high-temperature, high-pressure, or highly corrosive geological conditions-represents the most common type of municipal and residential heating application.
Selection for Direct-Buried Pipelines (Recommended Option)
In accordance with the *Technical Specification for Direct-Buried Hot Water Heating Pipelines in Urban Areas* (CJJ/T 81) and the standard atlas 24R426, direct-buried installation is the optimal solution. It aligns with urban landscape requirements, offers lower operation and maintenance costs, and results in reduced heat loss.
1. Primary Pipeline Types
Preferred options include pre-insulated, direct-buried pipes made of PE-RT Type II (heat-resistant polyethylene) or PB (polybutylene). Alternatively, steel pipes with a polyurethane foam insulation layer and a high-density polyethylene (HDPE) outer casing-commonly known as "black-jacket" insulated pipes-may be used.
2. Advantages of Selection
PE-RT Type II and PB plastic insulated pipes are resistant to aging caused by low-temperature hot water; they remain stable without deformation or leakage during long-term operation at a constant 75°C. Their high flexibility allows them to accommodate minor soil settlement, eliminating the need for numerous expansion joints and simplifying construction, which shortens project timelines. The polyurethane insulation layer features a high closed-cell ratio, providing excellent waterproofing and moisture resistance, as well as minimal underground heat loss-offering significant energy savings compared to above-ground (overhead) pipelines. "Black-jacket" insulated steel pipes offer superior mechanical strength, making them suitable for installation beneath roadways subject to heavy vehicular loads.
3. Applicable Scenarios and Restrictions
Suitable for: internal heating networks within residential complexes, branch lines, low-temperature hot water networks along secondary municipal roads, and standard soil conditions without significant groundwater accumulation. Prohibited: Areas with a consistently high water table, highly corrosive soil, or deep-trench installation along major, heavily trafficked thoroughfares (in such cases, reinforced steel pipes for direct burial must be used instead).
Selection Criteria for Above-Ground Piping (Used in Constrained Environments)
1. Core Piping Specifications
Prefabricated insulated steel pipes with a galvanized sheet-metal outer jacket are used. The carrier pipe consists of seamless steel, while the insulation layer is composed of either polyurethane or rock wool.
2. Advantages
This method eliminates the need for extensive excavation, remains unaffected by groundwater or soil corrosion, and facilitates easier inspection, maintenance, and replacement. It is more cost-effective than specialized direct-burial piping, making it well-suited for short-term retrofitting projects or temporary heating networks. The galvanized outer jacket provides resistance to UV radiation and outdoor weathering, ensuring suitability for long-term, above-ground operation.
3. Applicable Scenarios and Restrictions
Suitable for: Areas with high water tables, high excavation costs, or unstable soil conditions that preclude direct burial; temporary heating lines within industrial facilities; and sections of older residential areas where space for installation is limited. Prohibited: Prime urban landscape areas or locations along major arterial roads (due to negative impacts on the cityscape and the occupation of valuable space).